RTU-1 leak repair: braze circuit 1 suction line joint, evacuate, recharge, initial verification test. 30-day repair clock (due 2026-10-02).
Roof access via north ladder. Facilities contact Dana Ruiz on site until 3 pm.
Requires EPA 608
3201 Williams Dr
Georgetown, TX 78628
Equipment at this property
RTU-1 (25-ton rooftop)
Carrier 48TCFD28
4816C77777
Last serviced Sep 10, 2026
21 days left on the repair clock · Repair due Oct 1, 2026
3 previous visits
Sep 1, 2026 · Marcus
RTU-1 low cooling. Leak found at circuit 1 suction braze joint. Added 3.5 lb. Leak-rate threshold exceeded, repair case opened.
Apr 11, 2026 · Tommy
Spring maintenance RTU-1 and RTU-2. RTU-1 added 2.5 lb.
Nov 4, 2025 · Marcus
RTU-1 low cooling, added 3.0 lb.