10:46

Georgetown Pediatric Clinic

J-2026-0414 · Refrigerant leak repair

Syncing…
In progressArrival window 10:00–12:00

RTU-1 leak repair: braze circuit 1 suction line joint, evacuate, recharge, initial verification test. 30-day repair clock (due 2026-10-02).

Roof access via north ladder. Facilities contact Dana Ruiz on site until 3 pm.

Requires EPA 608

3201 Williams Dr
Georgetown, TX 78628

Equipment at this property

RTU-1 (25-ton rooftop)

Carrier 48TCFD28

4816C77777

R-410A62 lb14.5%

Last serviced Sep 10, 2026

21 days left on the repair clock · Repair due Oct 1, 2026

3 previous visits

  • Sep 1, 2026 · Marcus

    RTU-1 low cooling. Leak found at circuit 1 suction braze joint. Added 3.5 lb. Leak-rate threshold exceeded, repair case opened.

  • Apr 11, 2026 · Tommy

    Spring maintenance RTU-1 and RTU-2. RTU-1 added 2.5 lb.

  • Nov 4, 2025 · Marcus

    RTU-1 low cooling, added 3.0 lb.

5/10Checklist6PhotosR-410ARefrigerantEstimateInvoiceNotes