Search customers, jobs, equipment…
Prototype with sample data. No backend, nothing is saved.

RTU-1 (25-ton rooftop)

Carrier 48TCFD28 · 3201 Williams Dr, Georgetown, TX 78628

14 photosGenerate EPA 608 report

Leak repair case open

9.0 lb added over 12 months against a 62.0 lb full charge · Opened Sep 1, 2026 · Repair due Oct 1, 2026

Details

Make
Carrier
Model
48TCFD28
Serial
4816C77777
Installed
Mar 31, 2016
Status
In service
Age
10 years old
Refrigerant
R-410A
Full charge
62.0 lb
Capacity
25 ton

No warranty on file

Location: Roof, north

Photos

Refrigerant and leak rate

Trailing 12-month leak rate

14.5%Over the threshold
0%Threshold 10%40%

9.0 lb added over 12 months against a 62.0 lb full charge

Leak repair rule applies to this appliance

Thresholds and applicability are pending verification against current EPA rules. See the assumptions register.

Leak repair case open

Opened Sep 1, 2026

Repair due Oct 1, 2026

21 days left on the repair clock

  • Initial verification testPending
  • Follow-up verification testPending
Open repair job J-2026-0414

Refrigerant log

Every addition and recovery on this appliance. Retained for at least three years.

Export audit record
DateActionlbCylinderTechnicianNotes
Sep 10, 2026Recovered2.0 lbRCV-410-004Marcus ReedRecovered from circuit 1 for braze repair.
Sep 1, 2026Added3.5 lbCYL-410-026Marcus ReedTrailing 12-month additions now 9.0 lb of 62.0 lb charge (14.5%).
Sep 1, 2026Leak testMarcus ReedLeak located at circuit 1 suction line braze joint.
Apr 11, 2026Added2.5 lbCYL-410-022Tommy Nguyễn
Nov 4, 2025Added3.0 lbCYL-410-018Marcus Reed

Service history

  • Sep 10, 2026J-2026-0414Refrigerant leak repairIn progressRTU-1 leak repair: braze circuit 1 suction line joint, evacuate, recharge, initial verification test. 30-day repair clock (due 2026-10-02).Marcus Reed
  • Sep 1, 2026J-2026-0398AC repairCompletedRTU-1 low cooling. Leak found at circuit 1 suction braze joint. Added 3.5 lb. Leak-rate threshold exceeded, repair case opened.Marcus Reed
  • Apr 11, 2026J-2026-0171Heat pump maintenanceCompletedSpring maintenance RTU-1 and RTU-2. RTU-1 added 2.5 lb.Tommy Nguyễn
  • Nov 4, 2025J-2025-1240AC repairCompletedRTU-1 low cooling, added 3.0 lb.Marcus Reed